Product Overview
Control terminals
2
2
12 20 55
20 27 29 42 45
Illustration 2.7 Control Terminals
Terminal
Function
number
12
+24 V output –
18
Digital input
19
Digital input
20
Com
27
Digital input/
output
29
Digital input/
output/pulse
input
50
+10 V output –
53
Analog input *0–10 V/0–20 mA/
54
Analog input *0–10 V/0–20 mA/
55
Com
42
10 bit
45
10 bit
1, 2, 3
Relay 1
4, 5, 6
Relay 2
Table 2.1 Control Terminal Functions
* Indicates default setting.
NOTICE
PNP/NPN is common for terminals 18, 19, 27, and 29.
2.1.5 Serial Communication (Fieldbus)
Networks
These protocols are embedded in the frequency converter:
•
BACnet MSTP
•
Modbus RTU
•
FC Protocol
14
®
VLT
DriveMotor FCP 106/FCM 106
BUS TER.
OFF
ON
61 68 69
50 53 54
55
Configuration
Factory
setting
–
*PNP/NPN
Start
*PNP/NPN
No operation
–
–
*PNP/NPN
Coast inverse
*PNP/NPN
Jog
–
Ref1
4–20 mA
Ref2
4–20 mA
–
–
*0–20 mA/4–20 mA/DO Analog
*0–20 mA/4–20 mA/DO Analog
1, 2 NO 1, 3 NC
[9] Alarm
4, 5 NO 4, 6 NC
[5] Drive
running
Danfoss A/S © 06/2016 All rights reserved.
2.2 VLT
®
Memory Module MCM 101
®
The VLT
Memory Module MCM 101 is a small memory
plug containing data such as:
•
Firmware.
•
SIVP file.
•
Pump table.
•
Motor database.
•
Parameter lists.
The frequency converter comes with the module installed
from the factory.
1
1
®
VLT
Memory Module MCM 101
Illustration 2.8 Location of Memory Module
If the memory module becomes defect, it does not prevent
the frequency converter from working. The warning LED
on the lid flashes, and a warning shows in the LCP (if
installed).
Warning 206, Memory module indicates that either a
frequency converter runs without a memory module, or
that the memory module is defect. To see the exact reason
for the warning, refer to parameter 18-51 Memory Module
Warning Reason.
A new memory module can be ordered as a spare part.
Ordering number: 134B0791.
MG03M202