System Integration
Key
Dual-speed
operation
Key +/-
Key I
Run with reference Run with set-up 1 Run forward
Key II
Run with Jog
3
3
Key O
Table 3.12 Function
Terminal Dual-speed
operation
18
19
27
29
12
50
55
Table 3.13 Electrical Connections
Parameter
Parameter 5-10
Terminal 18
Digital Input
Terminal 18
Parameter 5-12
Terminal 27
Digital Input
Terminal 27
Parameter 5-13
Terminal 29
Digital Input
Terminal 29
More
parameters
Table 3.14 Parameter Settings
* Indicates factory setting.
Alarms are reset at every start. To avoid this reset, either:
•
Leave the brown wire unconnected, or
•
Set parameter 5-12 Terminal 27 Digital Input to [0]
No operation.
At power-up, the unit is always in stop mode. The set
reference is stored during power-down.
To set permanent start mode, disable the stop function on
the LOP as follows:
•
Connect terminal 12 to terminal 18.
•
Do not connect purple/grey wire to terminal 18.
40
VLT
Dual-mode
operation
Set reference
Run with set-up 2 Run reverse
Stop + Reset
Dual-mode
Dual-direction
operation
Purple
–
Brown
Green
Red
Yellow
Blue
Dual-speed
Dual-mode
Dual-direction
operation
operation
operation
Start*
Reset
Jog*
Select set-up
Parameter 3-
Parameter 0-10
Parameter 4-10 M
11 Jog Speed
Active Set-up
otor Speed
[Hz]
= [9] Multi set-
Direction = [2]
up
Both directions
Danfoss A/S © 06/2016 All rights reserved.
®
DriveMotor FCP 106/FCM 106
3.5 Special Conditions
Dual-direction
operation
3.5.1 Purpose of Derating
Consider derating when using the frequency converter:
•
•
•
operation
•
Gray
•
This section describes the actions required.
3.5.2 Derating for Ambient Temperature
and Switching Frequency
Refer to chapter 6.10 Derating According to Ambient
Temperature and Switching Frequency in this manual.
3.5.3 Automatic Adaptations to Ensure
Performance
The frequency converter constantly checks for critical levels
of:
•
•
•
•
Start reversing
As a response to a critical level, the frequency converter
can adjust the switching frequency and/or change the
switching pattern to ensure the performance of the
frequency converter. The capability for automatic output
current reduction extends the acceptable operating
conditions even further.
3.5.4 Derating for Low Air Pressure
The cooling capability of air is decreased at lower air
pressure.
•
•
•
At low air pressure (high altitudes).
At low speeds.
With long motor cables.
Cables with a large cross-section.
At high ambient temperature.
Internal temperature.
Load current.
High voltage on the DC link.
Low motor speeds.
Below 1000 m altitude no derating is necessary.
Above 1000 m altitude, reduce the ambient
temperature or the maximum output current.
-
Reduce the output by 1% per 100 m
altitude above 1000 m, or
-
Reduce the maximum ambient
temperature by 1 °C per 200 m altitude.
Above 2000 m altitude, contact Danfoss regarding
PELV.
MG03M202