Mains Supply; Protection And Features; Ambient Conditions - Danfoss VLT DriveMotor FCP 106 Design Manual

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Specifications

6.3 Mains Supply

Mains supply (L1, L2, L3)
Supply voltage
Mains voltage low/mains dropout:
During low mains voltage or a mains dropout, the frequency converter continues until the DC-link voltage drops below
the minimum stop level. This level typically corresponds to 15% below the lowest rated supply voltage of the frequency
converter. Power-up and full torque cannot be expected at mains voltage lower than 10% below the lowest rated
supply voltage of the frequency converter.
Supply frequency
Maximum imbalance temporary between mains phases
True power factor (λ)
Displacement power factor (COSφ)
Switching on the input supply L1, L2, L3 (power-ups)
Environment according to EN 60664-1 and IEC 61800-5-1
The unit is suitable for use on a circuit capable of delivering not more than:
100000 RMS symmetrical Amperes, 480 V maximum, with fuses used as branch circuit protection.
See Table 6.14 and Table 6.15 when using circuit breakers as branch circuit protection.

6.4 Protection and Features

Protection and features
Electronic motor thermal protection against overload.
Temperature monitoring of the heat sink ensures that the frequency converter trips when the temperature reaches
90 °C (194 °F) ±5 °C (41 °F). An overload temperature cannot be reset until the temperature of the heat sink is
below 70 °C (158 °F) ±5 °C (41 °F). However, these temperatures may vary for different power sizes, enclosures,
and so on. The frequency converter autoderating function ensures that the heat sink temperature does not reach
90 °C (194 °F).
The frequency converter motor terminals U, V, and W are protected against ground faults at power-up and start of
the motor.
When a motor phase is missing, the frequency converter trips and issues an alarm.
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the DC-link voltage ensures that the frequency converter trips when the DC-link voltage is too low
or too high.
The frequency converter is protected against ground faults on motor terminals U, V, and W.
All control terminals and relay terminals 01–03/04–06 comply with PELV (protective extra low voltage). However,
this compliance does not apply to grounded delta leg above 300 V.

6.5 Ambient Conditions

Environment
Enclosure protection rating
Enclosure protection rating FCP 106 between lid and heat sink
Enclosure protection rating FCP 106 between heat sink and adapter plate
FCP 106 wall mount kit
Stationary vibration IEC61800-5-1 Ed.2
Non-stationary vibration (IEC 60721-3-3 Class 3M6)
Relative humidity (IEC 60721-3-3; Class 3K4 (non-condensing))
Aggressive environment (IEC 60721-3-3)
Test method according to IEC 60068-2-43
Ambient temperature
MG03M202
Design Guide
Danfoss A/S © 06/2016 All rights reserved.
380–480 V ±10%
3.0% of rated supply voltage
≥0.9 nominal at rated load
Near unity (>0.98)
Maximum 2 times/min.
Overvoltage category III/pollution degree 2
IP66/Type 4X
5–95% during operation
40 °C (104 °F) (24-hour average)
50/60 Hz
6
6
1)
IP66/Type 4X
IP66/Type 4X
IP66
Cl. 5.2.6.4
25.0 g
Class 3C3
H2S (10 days)
67