Technical data

12.1

Rated conditions

Rated conditions
Ambient conditions
Ambient temperature
Permissible ambient temperature for operation
Height
Relative humidity
Degree of pollution
Overvoltage category
Degree of protection
2)
Mounting position
Vibration resistance
Harmonic oscillations (sine) according to EN 60068-2-
6/10.2008
Bumping (half-sine) according to EN 60068-2-27/02.2010
Noise (digitally controlled) according to EN 60068-2-
64/04.2009
Recommended range of continuous operation of the entire
control valve
Climate class
Storage
Transport
Operation
1)3)4)
The following applies to fail in place: Without explosion protection: -20 ... +60 °C (-4 ... +140 °F); with explosion protec-
1)
tion: T4: -20 ... +60 °C (-4 ... +140 °F) T6: -20 ... +50 °C (-4 ... +122 °F)
Max. impact energy 1 Joule for enclosure with inspection window 6DR5..0 and 6DR5..1 or max. 2 Joule for 6DR5..3 (in
2)
development).
At ≤ -10 °C (≤ 14 °F) the display refresh rate of the indicator is limited. When using position feedback module, only T4 is
3)
permissible.
-20 to +80 °C (-4 to +176 °F) for 6DR55..-0G ..., 6DR56..-0G ..., 6DR55..-0D ... and 6DR56..-0D...
4)
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
For use indoors and outdoors.
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-30 ... +80 °C (-22 ... +176°F)
1)
2000 m above sea level. At altitudes greater than 2000 m
above sea level, use a suitable power supply.
0 ... 100 %
2
II
IP66 to IEC/EN 60529 / NEMA 4X
Any; in wet environment, pneumatic connections and
outlet opening not upward
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axle
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axle
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
≤ 30 m/s² (98.4 ft/s²) without resonance peak
According to DIN EN 60721-3-4
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)
2K4, but -40 ... +80°C (2K4, but -40 ... +176°F)
4K3, but -30 ... +80 °C (4K3, but -22 ... +176 °F)