10.4.3

Remedial measures table 2

Fault profile (symptoms)
"CPU testt" blinks on the display
approximately every 2 seconds.
Piezo valve does not activate.
In the manual and automatic
modes, the actuator cannot be
moved or can be moved only in one
direction.
Piezo valve does not activate (a
gentle click sound is not audible
when the "+" or "-" buttons are
pressed in the manual mode.)
Fault table 2
See also
Repair/Upgrading (Page 238)
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Possible cause(s)
Water in the pneumatic block (due
to wet compressed air)
Moisture in the pneumatic block
The screw between the shrouding
cover and the pneumatic block has
not been tightened firmly or the
cover got stuck.
Dirt (swarf, particles) in the pneu-
matic block
Deposits on the contacts between
the electronic printed circuit board
and the pneumatic block may de-
velop due to abrasion owing to con-
tinuous loads resulting from strong
vibrations.
Alarm, error, and system messages
10.4 Fault correction
Corrective measures
At an early stage, this fault can be
rectified with a subsequent operat-
ing using dry air, if required, in a
temperature cabinet at 50 to 70°C.
Otherwise: Repair
Tighten the screw firmly; if required,
rectify the deadlock.
Repair or a new device; clean
and/or replace the built-in fine
screens.
Clean all contact surfaces with
spirit; if required, bend the pneu-
matic block contact springs.