Remedial Measures Table 1 - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Alarm, error, and system messages
10.4 Fault correction
See also
Remedial measures table 2 (Page 231)
Remedial measures table 3 (Page 232)
Corrective measures Table 4 (Page 233)
Remedial measures table 5 (Page 234)
10.4.2

Remedial measures table 1

Fault profile (symptoms)
Positioner remains in "RUN 1".
Positioner remains in "RUN 2".
Positioner remains in "RUN 3".
Positioner remains "RUN 5", does
not go up to "FINISH" (waiting time
> 5 min).
Fault table 1
230
Possible cause(s)
Initialization started from the end
position and
The response time of a maximum of
1 minute was not observed.
Supply air PZ not connected or
pressure of supply air PZ too low.
Transmission ratio selector and
parameter 2
"YAGL" and the real stroke do not
match.
Incorrectly set stroke on the lever.
Piezo valve does not activate.
Actuator travel time is too high.
"Gap" (play) in the positioner - ac-
tuator - control valve system
Corrective measures
A waiting time of up to 1 minute is
essential.
Do not start initialization from the
end position.
Ensure supply air PZ.
Check settings: see leaflet: Fig.
"Device view
" as well as param-
eters 2 and 3
Check the stroke setting on the
lever. See Table 2.
Open the restrictor completely
and/or set the pressure PZ (1) to
the highest permissible value.
Use a booster if required.
Part-turn actuator: check for the
firmness of the grub screw of the
coupling wheel
Linear actuator: check for the firm-
ness of the lever on the positioning
shaft.
Correct any other play between the
actuator and the control valve.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12