Parameterizing/addressing
9.4 Description of parameters
When the time interval expires, the calculated average value of reference is shown on the
display.
Note
Current average value of position
The respective current average value of position is displayed in the "19.PAVG" diagnostics
parameter. If no average value of position has been calculated, "COMP" is displayed in the
"19.PAVG" diagnostics parameter.
The factory setting is "IdLE".
P3.LEVL1 - threshold 1
Use this sub-parameter to set threshold 1 for the maximum deviation of the current average
value of position from the average value of reference. Set the threshold in a range from "0.1"
to "100.0".
The positioner triggers an error message if the difference between the average value of
position and the average value of reference exceeds threshold 1. The procedure to activate
and display this error message is described in the "XDIAG" parameter.
The factory setting is "2.0".
P4.LEVL2 - threshold 2
Use this sub-parameter to set threshold 2 for the maximum deviation of the current average
value of position from the average value of reference. Set the threshold in a range from "0.1"
to "100.0".
The positioner triggers an error message if the difference between the average value of
position and the average value of reference exceeds threshold 2. The procedure to activate
and display this error message is described in the "XDIAG" parameter.
The factory setting is "5.0".
P5.LEVL3 - threshold 3
Use this sub-parameter to set threshold 3 for the maximum deviation of the current average
value of position from the average value of reference. Set the threshold in a range from "0.1"
to "100.0".
The positioner triggers an error message if the difference between the average value of
position and the average value of reference exceeds threshold 3. The procedure to activate
and display this error message is described in the "XDIAG" parameter.
The factory setting is "10.0".