5. Insert the screens.
6. Connect the pipelines again.
7. Feed the pneumatic auxiliary power supply.
6.3
Repair/Upgrading
Send defective devices to the repairs department, together with information on the malfunction and the cause of the
malfunction. When ordering replacement devices, please provide the serial number of the original device. You can find the
serial number on the nameplate.
Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the
outside of the packaging. Any devices/replacement parts which are returned without a decontamination declaration will be
cleaned at your expense before further processing. For further details refer to the operating instructions.
See also
Return goods delivery note (http://www.siemens.com/processinstrumentation/returngoodsnote)
Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination)
6.4
Disposal
7

Technical data

7.1
All device versions
7.1.1

Operating conditions

Ambient temperature
● Permissible ambient temperature for operation
Degree of protection
1)
Mounting position
Vibration resistance
● Harmonic vibrations (sine) according to DIN EN 60068-2-
6/05.96
● Bump (half-sine) according to DIN EN 60068-2-29/03.95
● Noise (controlled digitally) according to DIN EN 60068-2-
64/08.95
● Recommended range of continuous operation of the entire
control valve
Climate class
● Storage
34
Devices identified by this symbol may not be disposed of in the municipal
waste disposal services under observance of the Directive 2002/96/EC on
waste electronic and electrical equipment (WEEE).
They can be returned to the supplier within the EC or to a locally approved
disposal service. Observe the specific regulations valid in your country.
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-30 ... +80 °C (-22 ... +176°F)
IP66 according to EN 60529 / NEMA 4X
Any; in wet environment, pneumatic connections and
outlet opening not upward
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axes
98.1 m/s² (321.84 ft/s²), 27 to 300 Hz, 3 cycles/axes
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 to 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 to 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
≤ 30 m/s² (98.4 ft/s²) without resonance peak
According to DIN EN 60721-3-4
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)