Parameterizing/addressing
9.4 Description of parameters
O1.LIMIT - Limit for number of changes in direction
Use this sub-parameter to set the base limit for the number of changes of direction of the
actuator. Set the base limit in a range from "1" to "1.00E8".
The factory setting is "1.00E6".
O2.FACT1 - factor 1
Use this sub-parameter to set the factor for the formation of limit threshold 1. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "O1.LIMIT" and
"O2.FACT1".
The threshold 1 error message is displayed when the limit threshold 1 is exceeded. The
procedure to activate and display this error message is described in the "XDIAG" parameter.
The factory setting is "1.0".
O3.FACT2 - factor 2
Use this sub-parameter to set the factor for the formation of limit threshold 2. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "O1.LIMIT" and
"O3.FACT2".
The threshold 2 error message is displayed when the limit threshold 2 is exceeded. The
procedure to activate and display this error message is described in the "XDIAG" parameter.
The factory setting is "2.0".
O4.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "O1.LIMIT" and
"O4.FACT3".
The threshold 3 error message is displayed when the limit threshold 3 is exceeded. The
procedure to activate and display this error message is described in the "XDIAG" parameter.
The factory setting is "5.0".
See also
Display of diagnostics values (Page 205)