Note
The value in the "YCDO" parameter is always smaller than that in "YCUP". The tight closing
function has a fixed hysteresis of 1%. The "YCDO" and "YCUP" parameters are relative to
the mechanical stops. The "YCDO" and "YCUP" parameters are independent of the values
set in the "'7.SDIR' Setpoint direction (Page 160)" and "'38.YDIR' Direction of manipulated
variable for display and position feedback (Page 166)" parameters.
9.4.2.13

'42.BIN1' / '43.BIN2' Function binary inputs

Setting option
Purpose:
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
• Binary input 1
Normally open
OFF
on
bloc1
bloc2
uP
doWn
StoP
PST
• Binary input 2
Normally open
OFF
on
uP
doWn
StoP
PST
These parameters determine the function of the binary inputs. The
possible functions are described below. The direction of action can
be adapted to a normally closed or normally open mode.
• BIN1 or BIN2 = On or -On
Binary messages from peripherals, e.g. from pressure or
temperature switches, are read over the communication
interface or fed through a logical OR combination with other
messages to trigger the error message output.
• BIN1 = bLoc1
Use this parameter value to interlock the "Configuration" mode
against adjustment. The lock is performed e.g. with a jumper
between terminals 9 and 10.
• BIN1 = bLoc2
If binary input 1 has been activated, the "Manual" as well as
"Configuration" modes are blocked.
Parameterizing/addressing
9.4 Description of parameters
Normally closed
OFF
-on
-uP
-doWn
-StoP
-PST
Normally closed
OFF
-on
-uP
-doWn
-StoP
-PST
167