Overview Of Advanced Diagnostics Parameters A To P - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Parameterizing/addressing
9.3 Parameter overview
9.3.3

Overview of advanced diagnostics parameters A to P

Introduction
These parameters are used to set the extended diagnostics functions of the positioner.
Note
Factory setting
Factory-set parameter values are printed in bold in the following table.
Note
Display
Parameters A to P and their sub-parameters are only displayed when the extended
diagnostics has been activated in parameter "'52.XDIAG' Activating for extended diagnostics
(Page 174)" with setting "On1", "On2" or "On3".
Overview parameter A
Parameter
Function
Partial stroke test with the following parameters:
A. PST
A1.STPOS
Start position
A2.STTOL
Start tolerance
A3.STRKH
Stroke height
A4.STRKD
Stroke direction
A5.RPMD
Ramp mode
A6.RPRT
Ramp rate
A7.FLBH
Behavior after failed PST
A8.INTRV
Test interval
A9.PSTIN
Reference stroke time for partial stroke test
AA.FACT1
Factor 1
Ab.FACT2
Factor 2
AC.FACT3
Factor 3
152
Parameter values
0.0 ... 100.0
0.1 ... 2.0 ... 10.0
0.1 ... 10.0 ... 100.0
uP / do / uP do
OFF / On
0.1 ... 1.0 ... 100.0
Auto / HOld / AirIn / AirOu
OFF / 1 ... 365
NOINI / (C)##.# / Fdini / rEAL
0.1 ... 1.5 ... 100.0
0.1 ... 3.0 ... 100.0
0.1 ... 5.0 ... 100.0
Operating Instructions, 09/2014, A5E00074631-12
Unit
%
%
%
%/s
Days
s
SIPART PS2 with and without HART