Functional Safety; Range Of Applications For Functional Safety; Safety Function - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

Functional safety

8.1

Range of applications for functional safety

The positioner is suitable for use on valves that satisfy the special requirements in terms of
functional safety up to SIL 2 in accordance with IEC 61508 or IEC 61511. The 6DR5.1.-0....-
....-Z C20 versions are available for this.
These are single-acting positioners for mounting on pneumatic actuators with spring return.
The positioner automatically depressurizes the valve actuator on demand or in case of faults,
which thus switches the valve to the specified safety position.
This positioner meets the following requirement:
● Functional safety up to SIL 2 in accordance with IEC 61508 or IEC 61511 for safe venting
See also
Functional safety in process instrumentation (http://www.siemens.com/SIL)
8.2

Safety function

Depressurizing of the connected actuator is the safety function for the SIPART PS2
positioner. The built-in spring brings the valve to the required safety position. Depending on
the direction of action of this spring, the valve is completely opened or closed.
The positioner starts the depressurizing process of the connected pneumatic actuator at the
latest 100 ms after the request. The progress of the depressurizing process depends on the
connections and properties of the pneumatic actuator.
This safety function can be triggered by:
● With 2-wire connection: a signal source with 0 mA.
● With 3/4-wire connection: a power supply source with 0 V.
Situations in which it is not possible to depressurize the actuator on demand or in the case of
a fault represent a dangerous failure.
Disregarding conditions for fulfilling the safety function
Disregard can result in a malfunction of the process plant or application, e.g. process
pressure too high, maximum level exceeded.
The mandatory settings and conditions are listed in sections "Settings (Page 142)" and
"Safety characteristics (Page 143)".
• These conditions must be met in order to fulfill the safety function.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
WARNING
8
139

Advertisement

Table of Contents
loading

This manual is also suitable for:

6dr53 series6dr51 series6dr52 seriesSipart ps2

Table of Contents