NOTICE
Condensation in the device
Damage to device through formation of condensation if the temperature difference between
transportation or storage and the mounting location exceeds 20 °C (36 °F).
• Before taking the device into operation let the device adapt for several hours in the new
NOTICE
Ambient temperature too high
Damage to cable sheath.
• At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an
NOTICE
Standard cable gland/torque
Device damage.
• Owing the reasons pertaining to tightness (IP enclosure rating) and the required tensile
• In the NPT version, the positioner is delivered with a coupling. When inserting a counter
Two-wire mode
NOTICE
Connection of voltage source to current input
Device damage if a voltage source is connected to the current input I
• Never connect the current input I
• Always use a voltage source with a maximum output current of I = 20 mA.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
environment.
ambient temperature at least 20 °C (36 °F) higher.
strength, only use the cables having a diameter ≥ 8 mm for standard M20x1.5 cable
gland, or use a suitable seal insert in case of smaller diameters.
piece in the coupling, ensure that the maximum permissible torque of 10 Nm is not
exceeded.
destroyed.
to a voltage source, otherwise the positioner may be
w
Connection
5.1 Basic safety instructions
(terminals 6 and 7).
w
71