'5.INITM' Initialization (manual)

Possible settings:
Purpose:
Description:
Factory setting:
9.4.2

Description of application parameters 6 to 52

9.4.2.1

'6.SCUR' Current range of setpoint

Requirement:
Possible settings:
Purpose:
Factory setting:
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
• NOINI
• no / ###.#
• Strt
Use this parameter to start the manual initialization process.
1. Select the "Strt" setting.
2. Then press the
button for at least 5 seconds.
If the positioner has already been initialized and if the "4.INITA"
and "5.INITM" values are set, it is possible to reset the positioner
to the non-initialized status. To do this, press the
least 5 seconds.
NOINI
• You have a SIPART PS2 in version "2-, 3-, 4-wire".
• Positioner is connected in accordance with the connection
graphics for 2-/3-/4-wire systems shown in sections "Device
6DR5..0/1/2/3-0N or 6DR5..5-0E (Page 73)" and "Device
6DR5..0/1/2/3-0E/D/F/G/K (Page 81)".
• 0 MA
• 4 MA
This parameter is used to set the current range of the setpoint.
The selection of the current range depends on the type of connec-
tion. The "0 MA" setting (0 to 20 mA) is only possible for three-wire
and four-wire connections.
4 MA
Parameterizing/addressing
9.4 Description of parameters
button for at
159