Corrective Measures Table 4 - Siemens 6DR50 Series Operating Instructions Manual

Electropneumatic positioners with and without hart/not explosion-proof/explosion-proof
Table of Contents

Advertisement

10.4.5

Corrective measures Table 4

Fault profile (symptoms)
In stationary automatic mode (con-
stant setpoint) and in "Manual"
mode, both piezo valves continually
switch alternately, and the actuator
oscillates around an average value.
Positioner doesn't move control
valve to the stop (at 20 mA).
Error table 4
See also
Cleaning of the screens (Page 236)
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Possible cause(s)
Stiction of the packing gland from
the control valve or actuator too
large
Looseness (play) in the position-
er/actuator/control valve system
Actuator too fast
Supply pressure too low. Load on
the feeding controller or system
output is too low.
Alarm, error, and system messages
10.4 Fault correction
Corrective measures
Reduce stiction or increase dead-
band of positioner (parameter "dE-
bA") until the oscillation stops.
Part-turn actuator: Check for firm
seating of set screw on coupling
wheel.
Linear actuator: Check for firm
seating of lever on positioner shaft.
Correct any other play between the
actuator and the control valve.
Increase travel times using throttle
screws.
If a quick travel time is needed,
increase the deadband (parameter
"dEbA") until the oscillation stops.
Increase supply pressure, insert
ballast converter
Select 3/4-wire mode
233