Technical Data - Siemens SIPART PS2 6DR5020 Series Manual

Electropneumatic positioner for linear and rotary actuators
Table of Contents

Advertisement

Technical Data

General data for basic device 6DR5xxx-xx
Travel range (linear actuators)
Angle or rotation (part-turn
actuators)
Installation
• On linear actuators
• On part-turn actuators
Controller
• Five-point switch
• Dead zone
dEbA = Auto
dEbA = 0.1 to 10%
• Controllable response time
A/D converter
• Scanning time
• Resolution
• Transmission error
• Temperature influence
Binary input BI1 (connected
electrically to I
current input)
w
Contact rating
Degree of protection
Mounting position
CE marking
• Emitted interference
• Noise immunity
Material of:
• Casing
- 6DR5
7 7
0-... (plastic)
- 6DR5
7 7
1-... (metal)
- 6DR5
5-... (metal)
7 7
• Pressure gauge block
Resistance to vibration
SIPART PS2 Manual
A5E00074631-01
3 to 130 mm (angle of feedback
shaft 16 to 90°)
30 to 100°
Using mounting kit 6DR4004-8V
and additional lever arm
6DR4004-8L if required on actua-
tors according to IEC 534-6
(NAMUR) with ledge, columns or
plane surface
Using mounting kit 6DR4004-8D
on actuators with fixing platform
according to VDI/VDE 3845 and
DIN 3337:
the mounting plate must be pro-
vided on the actuator side;
shaft with nut and M6 female
thread
Self-adjusting
Self-adjusting or
fixed setting
≥ 1.5 s,
reduced resolution with smaller
positioning times
10 ms
≤ 0.05 %
≤ 0.2 %
≤ 0.1 %/10 K
Can be used for floating contact
≤ 5 µ A at 3 V
IP 65 to EN 60 529
Any; in wet environment, pneu-
matic connections and exhaust
opening not upwards
Conforms to EMC guideline
89/336 EEC in compliance with
the following standards
EN 50 081-1
EN 50 082-2 and
NAMUR NE21 May 93
Glass-fiber-reinforced Macrolon
GK-AISi7Mg
GK-AISi7Mg
Aluminium AIMgSi, anodized
10 g (up to 100 Hz)
Pneumatic data
Supply (inlet air)
• Pressure
Air quality according to ISO 8573-1
• Size and density of particulates
• Pressure dew point
• Oil concentration
Unrestricted flow of:
3
• Inlet air valve [Nm
/h]
3
• Outlet air valve [Nm
/h]
Valve leakage
Throttle ratio
Consumption of inlet air in
stable state
Types of actuators
• In plastic casing
• In metal casing
• In flameproof casing
6
1.4 to 7 bar: sufficiently larger
than max. actuator pressure
(positioning pressure)
Class 2
Class 2 (min. 20 K below ambient
temperature)
Class 2
At
2 bar
4 bar
6 bar
4.1
7.1
9.8
8.2
13.7
19.2
-4
3
< 6 x 10
Nm
/h
Adjustable up to ∞ : 1
-2
3
< 3.6 x 10
Nm
/h
Single-action and double-action
Single-action
Single-action and double-action
101