G1.LEVL1 - threshold 1
Adjustment range:
Purpose:
Factory setting:
G2.LEVL2 - threshold 2
Adjustment range:
Purpose:
Factory setting:
G3.LEVL3 - threshold 3
Adjustment range:
Purpose:
Factory setting:
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
0.1 ... 10.0
Use this sub-parameter to set threshold 1 for the upper endstop in
percent. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between
the upper endstop and the initialization value undershoots thresh-
old 1. The procedure to activate and display this error message is
described in the "XDIAG" parameter.
1.0
0.1 ... 10.0
Use this sub-parameter to set threshold 2 for the upper endstop in
percent. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between
the upper endstop and the initialization value undershoots thresh-
old 2. The procedure to activate and display this error message is
described in the "XDIAG" parameter.
2.0
0.1 ... 10.0
Use this sub-parameter to set threshold 3 for the upper endstop in
percent. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between
the upper endstop and the initialization value undershoots thresh-
old 3. The procedure to activate and display this error message is
described in the "XDIAG" parameter.
4.0
Parameterizing/addressing
9.4 Description of parameters
191