12.4
Controller
Controller
Control unit
Five-point controller
•
Dead zone
•
dEbA = auto
dEbA = 0.1 ... 10 %
Analog-to-digital converter
Scanning time
•
Resolution
•
Transmission error
•
Temperature influence
•
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Adaptive
Adaptive
Can be set as fixed value
10 ms
≤ 0,05 %
≤ 0,2 %
≤ 0.1 %/10 K (≤ 0.1 %/18 °F)
Technical data
12.4 Controller
245