Motor Holding Brake Connection - Kollmorgen AKD2G-S Series Installation Manual

With functional safety option 1 sto - sil2
Hide thumbs Also See for AKD2G-S Series:
Table of Contents

Advertisement

AKD2G-S Installation, Safety 1 | 8   Electrical Installation

8.9.4 Motor Holding Brake Connection

A 24 V holding brake in the motor can be controlled directly by the drive. For proper function,
check voltage drop, measure voltage at brake input and check brake function (on and off).
Brake voltage supply via 24 V ±10% auxiliary voltage supply of the drive on X10. Minimum
and maximum brake current see Electrical Data (➜ # 36) respectively (➜ # 38).
AKD2G offers one motor brake output for every axis on connector X1 and X2 (➜ # 82).
Serious injury could result when the load is not properly blocked. This function does not
ensure functional safety.
Pinout X1 / X2
Pin Signal
B+ BR+
B- BR-
Wiring
Usually the brake lines are part of the Kollmorgen hybrid single cable connection to X1
respectively X2 (➜ # 78).
82
Kollmorgen | kdn.kollmorgen.com | Beta, December 2018
Connector
Usable for
X1
Primary motor brake axis 1
X2
Primary motor brake axis 2
No functional Safety!
Functional safety, e.g. with hanging load (vertical axes), requires an additional brake.
The Hardware Enable does not initiate a controlled stop but switches off the power stage
immediately.
Set parameter AXIS#.MOTOR.BRAKEIMM to 1 with vertical axes, to apply the brake
immediately after faults or Hardware Disable.
Description
Brake positive line
Brake negative line