AKD2G-S Installation, Safety 1 | 8   Electrical Installation

8.6 Power and Logic Voltage Supply (X3/X10)

8.6.1 Mains power supply (X3)

Drives in the AKD2G series can be supplied as follows:
AKD2G-Sxx-6V
AKD2G-Sxx-7V
Connection to other voltage types of AC supply networks is possible with an additional isol-
ating transformer.
Periodic overvoltages between phases (L1, L2, L3) and the housing of the drive must not
exceed 1000 V peak.
In accordance with IEC 61800, voltage spikes (< 50 µs) between phases must not exceed
1000 V. Voltage spikes (< 50 µs) between a phase and the housing must not exceed 2000 V.
Pin Signal
1
2
3
4
70
Kollmorgen | kdn.kollmorgen.com | Beta, December 2018
1, 2 or 3 phase industrial AC supply networks: 120 V or 240 V.
DC supply networks: on request.
3 phase industrial AC supply networks: 240 V, 400 V or 480 V.
DC supply networks: on request.
Description
PE
Protective earth
L1
3~ mains supply L1, 1~ supply L, DC supply +
L2
3~ mains supply L2
L3
3~ mains supply L3, 1~ supply N, DC supply -
8 pin, pitch 7.62 mm
optional T version
Wiring example:
1 phase AC supply (➜ # 73)
2 phase AC supply (➜ # 73)
3 phase AC supply (➜ # 74)
DC supply (➜ # 74)
AKD2G-Sxx-6V requires external EMC filter for use in
industrial environment, product category C.
Mating connector data see (➜ # 51).