Electrical Installation

4.8.1 Control Terminal Types

Figure 4.7 and Figure 4.8 show the removable adjustable
frequency drive connectors. Terminal functions and default
settings are summarized in Table 4.2 and Table 4.3.
4
4
Figure 4.7 Control Terminal Locations
Figure 4.8 Terminal Numbers
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage. FC
302 and FC 301 (optional in A1 enclosure) also
provide a digital input for STO function
Connector 2 terminals (+)68 and (-)69 for RS-485
serial communication connection
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software
18
Instruction Manual
4
1
12 13 18 19 27 29 32 33 20 37
2
3
61 68 69
39 42 50 53 54 55
Danfoss A/S © Rev. 09/2014 All rights reserved.
Terminal
Parameter
12, 13
-
18
5-10
19
5-11
32
5-14
1
33
5-15
27
5-12
29
5-13
20
-
37
-
39
-
42
6-50
50
-
53
6-1*
54
6-2*
55
-
Table 4.2 Terminal Description Digital Inputs/Outputs,
Analog Inputs/Outputs
Terminal description
Default
Description
setting
Digital inputs/outputs
+24 V DC
24 V DC supply
voltage for digital
inputs and external
transducers. Maximum
output current
200 mA (130 mA for
FC 301) for all 24 V
loads.
[8] Start
Digital inputs.
[10] Reversing
[0] No
operation
[0] No
operation
[2] Coast
For digital input or
inverse
output. Default setting
is input.
[14] JOG
Common for digital
inputs and 0 V
potential for 24 V
supply.
STO
Safe input.
Analog inputs/outputs
Common for analog
output.
[0] No
Programmable analog
operation
output. 0-20 mA or
4-20 mA at a
maximum of 500 Ω
+10 V DC
10 V DC analog
supply voltage for
potentiometer or
thermistor. 15 mA
maximum
Reference
Analog input. For
voltage or current.
Feedback
Switches A53 and A54
select mA or V.
Common for analog
input.