Electrical Installation

4.8.1 Control Terminal Types

Figure 4.7 and Figure 4.8 show the removable adjustable
frequency drive connectors. Terminal functions and default
settings are summarized in Table 4.3.
4
4
Figure 4.7 Control Terminal Locations
Figure 4.8 Terminal Numbers
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage.
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communication connection.
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output.
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software.
20
VLT
4
1
12 13 18 19 27 29 32 33 20 37
2
3
61 68 69
39 42 50 53 54 55
Danfoss A/S © 10/2014 All rights reserved.
®
AQUA Drive FC 202
Term-
inal
Parameter
12, 13
18
5-10
19
5-11
32
5-14
33
5-15
1
27
5-12
29
5-13
20
37
39
42
6-50
50
53
54
55
61
68 (+)
69 (-)
Default
setting
Terminal description
Digital Inputs/Outputs
-
+24 V DC
24 V DC supply voltage for
digital inputs and external
transducers. Maximum
output current 200 mA for
all 24 V loads.
[8] Start
[0] No
operation
[0] No
Digital inputs.
operation
[0] No
operation
[2] Coast
For digital input or output.
inverse
Default setting is input.
[14] JOG
-
Common for digital inputs
and 0 V potential for 24 V
supply.
-
Safe Torque
Safe input (optional). Used
Off (STO)
for STO.
Analog Inputs/Outputs
-
Common for analog
output.
Speed 0 -
Programmable analog
High Limit
output. 0–20 mA or
4–20 mA at a maximum of
500 Ω.
-
+10 V DC
10 V DC analog supply
voltage for potentiometer
or thermistor. 15 mA
maximum
6-1
Reference
Analog input. For voltage
or current. Switches A53
6-2
Feedback
and A54 select mA or V.
-
Common for analog input.
Serial Communication
-
Integrated RC filter for
cable shield. ONLY for
connecting the shield in
the event of EMC
problems.
8-3
RS-485 Interface. A control
card switch is provided for
8-3
termination resistance.
Relays
Description
MG20MA22