Control Terminal Types - Danfoss VLT AutomationDrive FC 303 Instruction Manual

Table of Contents

Advertisement

Installation
2
2
Figure 2.10 Control Wiring Access for A4, A5, B1, B2, C1 and C2
Enclosures
Please see Table 2.2 before tightening the covers.
Frame
A4/A5
B1
B2
C1
C2
* No screws to tighten
14°F Does not exist
Table 2.2 Tightening Torques for Covers (Nm)

2.4.5.2 Control Terminal Types

Figure 2.11 and shows the removable adjustable frequency
drive connectors. Terminal functions and default settings
are summarized in Table 2.3.
Figure 2.11 Control Terminal Locations
2-8
VLT
®
Manual
IP20
IP21
IP55
-
-
2
-
*
2.2
-
*
2.2
-
*
2.2
-
*
2.2
4
MG.33.AI.22 - VLT
AutomationDrive Instruction
Figure 2.12 Terminal Numbers
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24V
DC terminal supply voltage, and a common for
optional customer supplied 24V DC voltage. FC
302 and FC 301 (optional in A1 enclosure) also
provide a digital input for STO (Safe Torque Off)
function.
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
Connector 3 provides two analog inputs, one
IP66
analog output, 10V DC supply voltage, and
2
commons for the inputs and output
2.2
Connector 4 is a USB port available for use with
2.2
the MCT 10 Set-up Software
2.2
2.2
Also provided are two Form C relay outputs that
are in various locations depending upon the
adjustable frequency drive configuration and size
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
See 10.2 General Technical Data for terminal ratings details.
Terminal Parameter
12, 13
1
18
19
32
33
®
is a registered Danfoss trademark
1
12 13 18 19 27 29 32 33 20 37
2
3
61 68 69
39 42 50 53 54 55
Terminal description
Default
setting
Description
Digital inputs/outputs
-
+24V DC
24V DC supply
voltage. Maximum
output current is
200mA total (130mA
for FC 301) for all 24V
loads. Useable for
digital inputs and
external transducers.
5-10
[8] Start
5-11
[10] Reversing
5-14
[0] No
Digital inputs.
operation
5-15
[0] No
operation

Hide quick links: