Restoring Default Settings; Basic Programming; Commissioning With Smartstart - Danfoss VLT AutomationDrive FC 301 Instruction Manual

0.25–75 kw
Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Commissioning
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter Status, or press
[Main Menu] once to enter the Main Menu.
View changes
Quick Menu Q5 - Changes Made lists all parameters
changed from default settings.
The list only shows parameters, which have been
changed in the current edit set-up.
Parameters, which have been reset to default
5
5
values, are not listed.
The message Empty indicates that no parameters
have been changed.

5.3.6 Restoring Default Settings

NOTICE!
Risk of losing programming, motor data, localization,
and monitoring records by restoration of default
settings. To provide a backup, upload data to the LCP
before initialization.
Restoring the default parameter settings is done by initiali-
zation of the adjustable frequency drive. Initialization is
carried out through 14-22 Operation Mode (recommended)
or manually.
Initialization using 14-22 Operation Mode does not
reset adjustable frequency drive settings, such as
operating hours, serial communication selections,
personal menu settings, fault log, alarm log, and
other monitoring functions.
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
Recommended initialization procedure, via
14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to 14-22 Operation Mode and press [OK].
3.
Scroll to [2] Initialization and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
26
Instruction Manual
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
Manual initialization procedure
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
adjustable frequency drive information:

5.4 Basic Programming

5.4.1 Commissioning with SmartStart

The SmartStart wizard enables fast configuration of basic
motor and application parameters.
NOTICE!
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
Danfoss A/S © Rev. 09/2014 All rights reserved.
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
15-00 Operating hours
15-03 Power-ups
15-04 Over Temps
15-05 Over Volts
SmartStart starts automatically, at first power-up
or after initialization of the adjustable frequency
drive.
Follow the on-screen instructions to complete the
commissioning of the adjustable frequency drive.
Always reactivate SmartStart by selecting Quick
Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to chapter 5.4.2 Commissioning via
[Main Menu] or the Programming Guide.
MG33AP22