Electrical Installation
1
9
10
L1
L2
L3
PE
1
PLC
2
Adjustable frequency drive
3
Output contactor
4
Cable clamp
5
Cable insulation (stripped)
6
Cable connector
Figure 4.2 EMC-compliant Electrical Connection
For more information about EMC, see chapter 4.2 EMC-compliant Installation
NOTICE!
EMC INTERFERENCE
Run cables for input power, motor wiring and control wiring in three separate metallic conduits. Failure to isolate
power, motor and control cables can result in unintended behavior or reduced performance. Minimum 7.9 in [200 mm]
clearance between power, motor and control cables is required.
MG33AP22
Instruction Manual
2
11
8
7
Motor, 3--phase and PE (shielded)
8
Line power, 3--phase and reinforced PE (non-shielded)
9
Control wiring (shielded)
10
Potential equalization min. AWG 6 [16 mm
Clearance between control cable, motor cable and line cable:
11
Min. 7.9 in [200 mm]