Connect the 8720MC-RPS Unit

Wiring Requirements

Terminals
Mains input
power
DC Bus power
Ground Stud
Control terminal
(TB2)
(1) Terminal must be UL Listed. JST = Japan Solderless Terminal Co.
Terminals
Mains input
power
DC Bus power
Ground Stud
Control terminal
(TB2)
Control terminal
(TB4)
(1) Terminal must be UL Listed. JST = Japan Solderless Terminal Co.
46
Wires must be copper with 75 °C (167 °F) minimum rating. Phasing of main
AC power is arbitrary and earth ground connection is required for safe and
proper operation.
Refer to
Power Wiring Examples
IMPORTANT The National Electrical Code and local electrical codes take precedence
Table 14 - 8720MC-RPS065 Wiring Requirements
Connects to
Screw Size
Terminals
L1, L2, L3
M6
P, N
G
L1_AUX
L2_AUX
L3_AUX
M4
PR1, PR2, PR3
MC1, MC2
Table 15 - 8720MC-RPS190 Wiring Requirements
Connects to
Screw Size
Terminals
L1, L2, L3
M10
P, N
G
M8
L1_AUX
L2_AUX
L3_AUX
M4
PR1, PR2, PR3
PR4, PR5, PR6
+24V3, 0V3, SENS,
+24V2, 0V2,
M4
MC1, MC2
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
on
page 121
over the values and methods provided.
Wire Size
2
mm
(AWG)
22 (4)
2 (14)
Wire Size
2
mm
(AWG)
38 (2)
(two parallel wires)
38 (2)
3.5 (12)
2 (14)
for interconnect diagrams.
Torque Value
Pressure
(1)
Terminal
N•m (lb•in)
JST 22-S6
2.9 (26)
or R22-6
JST 2-M4
1.2...1.4
or R2-4
(11...12)
Torque Value
Pressure
(1)
Terminal
N•m (lb•in)
JST R38-10 (x6)
10...12
(89...106)
JST R38-10 (x4)
5.5...6.6
JST R38-10 (x1)
(48...57)
1.2...1.4
JST 3.5-R4
(11...12)
1.2...1.4
JST 2-M4
(11...12)

Hide quick links: