Sequence Signal Wiring - Allen-Bradley 8720MC-RPS065 User Manual

Regenerative power supply
Table of Contents

Advertisement

Sequence Signal Wiring

Sequence output signals are provided from the sequence signal terminal block
(TB3) of the regulator board to indicate the unit status.
Follow these guidelines when installing sequence signal wiring:
• Use twisted pair cable of 0.2...0.5 mm
line.
• Separate the sequence signal wiring from the power wiring (main power
supply wiring, control power wiring, and DC-bus power wiring). Failure
to observe this precaution could result in damage to the 8720MC-RPS
unit.
• Use a separate (dedicated) wireway for the sequence signal wiring.
• Do not route the sequence signal wiring near any equipment that
produces electromagnetic interference.
Figure 32 - Typical Sequence Control Signal Connections
Terminal Block TB3 on Regulator Board
2.2K
1K
2.2K
1K
2.2K
1K
8720MC-RPS Unit
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
MC
RST
PWR
0V
+VC
24V
4.64K
0VC
COM
4.64K
IP
IP
4.64K
RDY
RDY
FR
To an external error detection sequence circuit.
FR
Connect the 8720MC-RPS Unit
2
(22...20 AWG) for the signal
Load Equipment
Chapter 5
67