Chapter 4
Connector Data and Feature Descriptions
38
ATTENTION: Do not alter the settings of any jumpers not described in this
manual. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
Jumpers JP1/JP2 and switch SW7 are set to these default settings at the
factory.
Table 12 - Jumper and Switch Default Settings
Jumper
Function
JP1
Enable Operation
JP2
Enable Inspection Mode
SW6
Reset
IMPORTANT Do not press the reset switch SW6 during operation.

Switch SW7 Settings

SW7 settings depend on the configuration of leader and follower units in your
application. This switch is used to stop the switching of transistors that
produces the PWM waveform by interrupting the base signal from the power
modules. To interrupt the base signal, turn the switch to the OFF position.
Switch SW7 consists of four switches:
• SW7-1, SW7-2, and SW7-3 are allocated to the leader unit and follower
units 1 and 2. In the case of a leader with paralleled follower units, it is
possible to interrupt the base signal of each unit by turning the
corresponding switch to the OFF position.
• Keep SW7-4 in the OFF position.
• When two units are connected in parallel, turn SW7-1 and SW7-2 to
the ON position
• When three units are connected in parallel, turn SW7-1, SW7-2, and
SW7-3 to the ON position.
Figure 17 - Switch SW7 Positions
Follower Unit 2
Follower Unit 1
Leader Unit
ON
ENABLE
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
Description
Short this jumper to start the switching operation of transistors when the
RUN sequence input is enabled. Keep this jumper closed.
Keep this jumper open.
Pressing this switch resets the CPU.
SW7-4
SW7-3
SW7-2
SW7-1
OFF
BASE BLOCK