Safety Features; Installation Notes; Terminals And Wiring - Allen-Bradley 1606-XLB Reference Manual

Basic power supply 5 a
Table of Contents

Advertisement

Safety Features

Installation Notes

Terminals and Wiring

Attribute
Input/output separation
double or reinforced insulation
Class of protection
Isolation resistance
Touch current
(leakage current)
• Use appropriate copper cables that are designed for minimum operating
temperatures of:
– 75 °C (167 °F) for ambient up to 55 °C (131 °F) minimum.
– 90 °C (194 °F) for ambient up to 70 °C (158 °F) minimum.
• Follow national installation codes and installation regulations
• Verify that all strands of a stranded wire enter the terminal connection.
• Do not use the power supply without a PE connection.
• Secure unused terminal compartments tightly.
• Ferrules are allowed.
The terminals are IP20 Fingersafe constructed and suitable for field- and
factory wiring.
Attribute
Terminal type
Solid wire, max
Stranded wire, max
American Wire Gauge
max wire diameter
Wire stripping length
Screwdriver
Recommended tightening torque
Rockwell Automation Publication 1606-RM055A-EN-P - December 2016
1606-XLB120E
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
I
PE (Protective Earth) connection required
> 100 MOhm
input to output, 500V DC
typ 0.21 mA/0.46 mA 100V AC, 50 Hz, TN-,TT-mains/IT-mains
typ 0.30 mA/0.65 mA 120V AC, 60 Hz, TN-,TT-mains/IT-mains
typ 0.33 mA/0.72 mA 230V AC, 50 Hz, TN-,TT-mains/IT-mains
< 0.27 mA/0.56 mA
110V AC, 50 Hz, TN-,TT-mains/IT-mains
< 0.38 mA/0.78 mA
132V AC, 60 Hz, TN-,TT-mains/IT-mains
< 0.43 mA/0.90 mA
264V AC, 50 Hz, TN-,TT-mains/IT-mains
Input and Output Terminals
Screw terminals
2
6 mm
2
4 mm
AWG 20-10
2.8 mm (including ferrules)
7 mm (0.28 in.)
3.5 mm slotted or cross-head No 2
1 N•m (9 lb•in)
Basic Power Supply 5 A
DC-OK Signal Terminal
Push-in terminals
2
1.5 mm
2
1.5 mm
AWG 28-16
1.6 mm (including ferrules)
7 mm (0.28 in.)
Not required
Not applicable