Install The Harmonic Filter (8720Mc-Rps065 Units Only); Install The Emc Line Filter (8720Mc-Rps065 Units Only); Install The Line Filter (8720Mc-Rps190 Units Only) - Allen-Bradley 8720MC-RPS065 User Manual

Regenerative power supply
Table of Contents

Advertisement

Install the Harmonic Filter (8720MC-RPS065 units only)

Install the 8720MC-HF-B2 harmonic filter to remove high-order harmonics
generated by the switching operation of the AC input power modules. Wire
size for the 8720MC-HF-B2 harmonic filter is 3.5 mm
IMPORTANT Connect the harmonic filter on the incoming AC line-side of the AC

Install the EMC Line Filter (8720MC-RPS065 units only)

An AC (EMC) line filter is required for meeting the requirements of CE.
Install a line filter for three-phase AC input power and single-phase AC power
for the main magnetic contactors. Line filters are used in power supply and
power regeneration configurations.
Table 23 - Line Filters for 8720MC-RPS065 Units
8720MC-RPS
Cat. No.
8720MC-RPS065BM
8720MC-RPS065BS

Install the Line Filter (8720MC-RPS190 units only)

The 8720MC-EF190-VB (EMC) line filter unit contains line filter, magnetic
contactor, varistor, harmonic filter, and is used with the
8720MC-RPS190BM and 8720MC-RPS190BS regenerative power supplies.
Because the 8720MC-EF190-VB unit is completely assembled, the wiring can
be simplified in combination with 8720MC-LR10-100B reactors. For wiring
the 8720MC-EF190-VB unit, refer to
Table 24 - Recommended Power Wire Sizes
Terminal Block
Terminals
Mains (input)
L1, L2, L3
Mains (output)
L4, L5, L6
Ground (earth)
G
(1) UL-Listed wires must be lugged by attached lugs. JST is Japan Solderless Terminal Co.
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
contactor.
Three-phase AC Power for
AC Input Power Line
Allen-Bradley®
Soshin Electric PN Schaffner PN
Cat. No.
8720MC-RFI80
HF3080C-TOA
Screw Size
Wire Size
M8
Larger than 38 mm
(2-2 AWG in parallel)
M10
M8
Larger than 38 mm
Connect the 8720MC-RPS Unit
2
(12 AWG).
Single-phase AC Power for
Main Magnetic Contactor
Soshin Electric PN
FN2010-6-06
NF2005A-YX
Figure
25,
Figure
26, and
Figure
(1)
Attached Lug
JST, R38-8 (M8)
(6 pieces)
2
-2 in parallel
JST, R38-10 (M10)
(6 pieces)
JST, R38-8 (M8)
2
(2 AWG)
(1 piece)
Chapter 5
27.
Torque
5.5...6.6 N•m
(48...57 lb•in)
10...12 N•m
(89...106 lb•in)
5.5...6.6 N•m
(48...57 lb•in)
63