Access And Clear The Error Log - Allen-Bradley 8720MC-RPS065 User Manual

Regenerative power supply
Table of Contents

Advertisement

Chapter 8
Troubleshoot the 8720MC-RPS Unit

Access and Clear the Error Log

104
The following procedure shows how to access and clear the error log. Note that
you cannot clear a single entry from the error log. The entire log will be cleared
simultaneously by using this procedure.
1. Press PRG.
The operation panel is in Program
mode, the user parameter is
displayed, and the PROGRAM
status indicator tuns ON.
2. Press
until Err is displayed.
3. Press ENT.
With no errors present,
0--- is displayed.
With errors present, the last error
that occurred is displayed.
4. Press RST.
Pressing RST while the error log is
displayed clears the error log and
Err is displayed again, indicating
that the error log is empty.