Important User Information Environment and Enclosure Preventing Electrostatic Discharge North American Hazardous Location Approval Install Your Power Supply Module Connect Wiring for your Power Supply Module Diagnostic Indicator Specifications Derating Curve for 1794-PS3 (for any mounting other than horizontal) Mounting Dimensions...
2 FLEX I/O Power Supply Modules Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local Rockwell Automation Sales Office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
FLEX I/O Power Supply Modules Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
Page 4
4 FLEX I/O Power Supply Modules ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
FLEX I/O Power Supply Modules North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 1794-PS13 and 1794-PS3. The following information applies when Informations sur l’utilisation de cet operating this equipment in hazardous équipement en environnements dangereux: locations: Products marked "CL I, DIV 2, GP A, B, C, D"...
Do not attempt to operate an entire FLEX I/O system with the 1794-PS13 power supply. The 1794-PS3 power supply provides sufficient 24V DC power to operate 10 adapter modules. You can use this 1794-PS3 power supply to operate an entire FLEX I/O system. 1794-PS3 1794-PS13...
FLEX I/O Power Supply Modules Install Your Power Supply Module 1794-PS13 shown ATTENTION: During mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up. Hook the lip on the rear of the power supply module onto the top of the DIN rail, and rotate the power supply module onto the rail.
Power POWER SUPPLY 1794-PS3 1794-PS3 shown Terminals A, B and C are 120/230V AC supply terminals. Terminals D, E and F are available to daisychain this 120/230V AC power to other 1794-PS power supply modules. If applying 120/230V AC power to the power supply, you can also power the corresponding 120/230V AC modules in your FLEX I/O system.
Page 9
FLEX I/O Power Supply Modules Repeat steps 3 and 4 using terminals I and J for the second adapter. ATTENTION: The total length of wire for terminals H, I, J and G must not exceed 3m (9.8ft). Exceeding the 3m (9.8ft) length can reduce noise immunity. Connections D, E and F are used to pass 120/230V AC power to adjacent 1794 power supplies, or to power any corresponding120/230V AC modules in your FLEX I/O system.
Output voltage is greater than 20.4V DC, but less than 28V DC No power applied to the power supply Output voltage exceeded 35V DC, and overvoltage protection shut the unit down Output current is above 1.4A (1794-PS13) or above 3.2A (1794-PS3) Publication 1794-IN069E-EN-P - September 2018...
FLEX I/O Power Supply Modules Specifications General – 1794-PS13 and 1794-PS3 Attribute 1794-PS13 1794-PS3 Dimensions, approx. 87 x 69 x 69 mm 87 x 94 x 69 mm H x W x D 3.4 x 2.7 x 2.7 inches 3.4 x 3.7 x 2.7 inches...
12 FLEX I/O Power Supply Modules Output – 1794-PS13 and 1794-PS3 Attribute 1794-PS13 1794-PS3 Minimum load 0 mA 50 mA Output surge Sufficient to drive 4 adapters Sufficient to drive 10 adapters Overvoltage protection Output internally limited to 35V DC. Cycle power to re-energize.
Page 13
EN 61000-6-4; Industrial Emissions Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 (1794-PS3 only) Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation See the Product Certification link at http://www.rockwellautomation.com/products/certification...
14 FLEX I/O Power Supply Modules At the end of its life, this equipment should be collected separately from any unsorted municipal waste. Derating Curve for 1794-PS3 (for any mounting other than horizontal) Max. Output Current Ambient Temperature o C The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V DC supply voltages and ambient temperatures.
= Secure DIN rail approximately every 200 mm Millimeters (Inches) (2.0) 24V DC (3.2) Power POWER SUPPLY 1794-PS3 (3.4) (1.2) (3.7) 1794-PS3 87H x 95W x 69D (3.4H x 3.7W x 2.7D) = DIN rail = Secure DIN rail approximately every 200 mm...