Circuit Breaker/Fuse Selection

The 8720MC-RPS unit does not contain a circuit breaker. Install an adequate
circuit breaker on the AC input power line. When an earth leakage breaker is
used, select a breaker equipped with harmonic suppressor.
Provide the required quantity of circuit breakers with supplemental contact
(CB) for all units connected in parallel. Because supplemental contact of this
circuit breaker does not conform with a load of 5 mA, use a relay with less than
5 mA for connection when a supplemental contact is connected with sequence
input PWR.
Table 3 - Circuit Protection Specifications
8720MC-RPS
Input Voltage
Cat. No.
(three-phase) nom
8720MC-RPS065BM
8720MC-RPS065BS
324...506V AC
8720MC-RPS190BM
8720MC-RPS190BS
(1) Because the supplemental contact of this circuit breaker does not conform with load of 5mA, a relay with less than 5mA should be used for connection when a
supplemental contact is connected with sequence input PWR.

Contactor Specifications

To help prevent electrical noise, peripherals of the 8720MC-RPS065 unit such
as magnetic contactors and relays must be provided with adequate surge
suppressor. Use CR filter for AC circuit and inverse-parallel diodes for DC
operation circuit.
The 8720MC-EF190-VB EMC filters, when used with 8720MC-RPS190
units provides the magnetic contactor.
Table 4 - Input Power Contactor Specifications
8720MC-RPS
Cat. No.
8720MC-RPS065BM
8720MC-RPS065BS
8720MC-RPS190BM
8720MC-RPS190BS
(1) Select an adequate operating coil for the magnetic contactor within the range of 100...230V AC depending on the applied
(2) Where x is the voltage suffix code of the operating coil.
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
Amp
Fuji Electric Circuit
Rating
Breaker (or equivalent)
100 A
BW100EAGU-3P100
350 A
BW400SAGU-3P350
Allen-Bradley® Contactor
Cat. No.
(2)
100-C43x10
Included with 8720MC-EF190-VB EMC filter units.
voltage.
Plan and Mount the 8720MC-RPS Installation
Input Power Protection
(1)
Mersen Fuse
A070UD30KI100
A070UD30KI0315
(1)
Fugi Electric Contactor
Cat. No.
SC-N2S (UL listed component)
(CE marked)
Chapter 2
DC-bus Protection
Mersen Fuse
A130UD70LI100
A130UD71LLI0350
(1)
17