Chapter 5
Connect the 8720MC-RPS Unit
Ground the Drive System
Braided Ground Straps
12 mm (0.5 in.) by 0.8 mm (0.03 in.).
Keep straps as short as possible.
44
All equipment and components of a machine or process system must have a
common earth-ground point that is connected to chassis. A grounded system
provides a ground path for protection against electrical shock. Grounding your
modules and panels minimize the shock hazard to personnel and damage to
equipment caused by short circuits, transient overvoltages, and accidental
connection of energized conductors to the equipment chassis.
ATTENTION: The National Electrical Code contains grounding requirements,
conventions, and definitions. Follow all applicable local codes and
regulations to safely ground your system.
For CE grounding requirements, refer to
Ground the System Subpanel
Ground 8720MC-RPS units to a bonded cabinet ground bus with a braided
ground strap. Keep the braided ground strap as short as possible for optimum
bonding.
Figure 20 - Connect the Ground Terminal
L2
L1
L3
READY
READY
FAUL T
FAUL
PROGRAM
PROGRAM
RST PRG ENT
E
P
N
4
Refer to the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001, for more information.
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
EMC Compliance
8720MC Regenerative Power Supply
(8720MC-RPS190 is shown)
A
V
kW
kW
Item
Description
1
1
Ground screw (green) 2.0 N•m (17.7 lb•in), max
2
Braided ground strap (customer supplied)
2
3
Ground grid or power distribution ground
3
4
Bonded cabinet ground bus (customer supplied)
on
page
65.