Parameter setting examples – ACS355

Speed control using the CiA 402 velocity mode (vl)

This example shows how to configure a speed control application
that uses the velocity mode (vl) of the CiA 402 profile.
When configuring the master, you need to map the following
objects to the transmit and receive PDOs. For an example, see
section
Mapping objects required for controlling the drive
page 66.
CANopen
Output data
object
0x6040
Control word
0x6042
Target velocity
The table below gives the recommended drive parameter settings.
Drive parameter
9802 COMM PROT SEL
5101 FBA TYPE
5102 FB PAR 2
(PROFILE)
5103 FB PAR 3
(NODE ID)
3018 COMM FAULT
FUNC
3019 COMM FAULT
TIME
5127 FBA PAR
REFRESH
CANopen
object
0x6041
0x6044
Setting for ACS355
drives
4 = EXT FBA
1)
136 = ETH Pwrlink
0 (= CiA 402)
2)
3
2)
1 = FAULT
2)
3.0 s
1 = REFRESH
Start-up 41
Input data
Status word
Vl control effort
Description
Enables communication between
the drive and the fieldbus adapter
module.
Displays the type of the fieldbus
adapter module.
Selects the CANopen device
profile CiA 402.
Defines the address of the
device.
Enables fieldbus communication
fault monitoring.
Defines the fieldbus
communication break supervision
time.
Validates the FEPL configuration
parameter settings.