Siemens Sinumerik 802D sl Instruction Manual page 148

Hide thumbs Also See for Sinumerik 802D sl:
Table of Contents

Advertisement

Creating a Drive Project
10.2
Operating the control panel in STARTER (with the motor rotating)
Table 10-1
Signal (control
panel)
ON/OFF1
ON/OFF2
ON/OFF3
Pulse enable
Enable ramp-
function gene-
rator
Start/stop
ramp-function
generator
Setpoint
enable
Fig. 10-36 Enables
5. As shown in Fig. 10-36, click the Enables field to set the commands for enabling the
control words in the drive system.
Fig. 10-37 Incoming supply control priority
6. Click Infeed control priority. The supply (Active Line Module) is turned on.
7. Before starting the motor by choosing Motor on (see Fig. 10-38), you have to make the
following settings:
10-146
Control word for the sequence control
PROFIdrive
bit no. in CTW
sequence control
Bit 0
0 = OFF (OFF1), stop via ramp-function generator, followed by pulse
block
1 = ON, service condition
Bit 1
0 = Coast down (OFF2), pulse block, motor coasts to standstill
1 = Do not coast down, operating condition
Bit 2
0 = Rapid stop (OFF3)
1 = No rapid stop, service condition
Bit 3
0 = Disable operation, pulse suppression
1 = Enable operation, enable pulses
Bit 4
0 = Set ramp-function generator to 0
1 = Enable ramp-function generator
Bit 5
0 = Freeze ramp-function generator, retain current output value
1 = Re-enable ramp-function generator; will follow the input value
Bit 6
1 = Enable setpoint
0 = Inhibit setpoint and set to 0
Click the
Enables field.
Meaning
Click
Infeed control priority.
SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition
6FC5 397-0CP10-1BA0