HOW TO SETUP THE START-UP POWER (STRTUP)
During the window of time between when power is first applied to the sensor and the sensor acquires the level
reading, the output current can be preset in order to avoid any false alarms during this window. The options for
start-up are 4mA, 12mA, 20mA or 22mA.
1. In
TOP-LEVEL
OUTPUT.
2. Select STRTUP.
3. Select 4mA, 12mA, 20mA or 22mA.
a. Press and hold OK on the selected
setting for 2 seconds then release.
b. To cancel STRTUP, Select EXIT.
4. Select EXIT to return to TOP-LEVEL MENU.
MN310140 Rev A3
(continued)
MENU
mode,
select
Section Eight
47
|