Note: If using the Flowline LM90-1001 (liquid tight fitting) on the ½” conduit, the cable minimum is 0.170” (4.3mm) and the maximum is 0.450” (11.4mm).
Page 3
PC. ® STEP P 1: INSTALL L WEBCAL SOFTWARE wnload WebC Cal® softwar re from w.flowline.co m/webcal-so oftware onto o a PC with t the following g minimum spec cifications: ® ® Wind...
Page 4
STEP P 4 - TRANS MITTER CON NFIGURATIO Conf figure the Lo oop Fail-Safe e, Output at Empty and Startup Con ndition for the e transmitte Loop Fail- -safe o Sets t the default o output when the tr ansmitter do oes not receiv...
Configuration is now complete. ® Disconnect the USB Fob before continuing to the next step: ® Mounting the EchoTouch ® ® * For complete information on the WebCal software, please refer to the WebCal manual located at flowline.com/webcal-software. QS300820 Rev A2...
® CONFIGURING ECHOTOUCH (DISPLAY) – US06 SERIES ONLY TOP-LEVEL MENU The transmitter is configured with the three buttons on the transmitter face (UP, DOWN and OK) and the transmitter’s LCD. To access the transmitter’s Top-level menu, simply hold down the OK button for five seconds.
2 seconds then release. 3) Select EXIT to return to the TOP-LEVEL MENU. TROUBLESHOOTING ® If you face any issues not addressed in this Quick Start, please refer to the EchoTouch Manual located on Flowline’s website at www.flowline.com. QS300820 Rev A2...
Page 8
Diameter or 12” Height to 6” Inner Diameter). LM52-2890 Installation in open tanks and sumps: Use Flowline's LM50-1001 side mount bracket. Note: The Side Mount Bracket (LM50 series) is not designed for use with stand pipes or as a method to secure stand pipes.
Page 9
IMPORTANT MOUNTING GUIDELINES 1) Never mount the transmitter at an angle. 2) Liquid should never enter the dead band. 3) Mount at least 3” from the side wall. 4) Never mount the transmitter in a vacuum. 5) Do not obstruct the transmitter’s beam width with objects underneath the transmitter. 6) Never mount in the center of a dome top tank.
Intrinsically Safe applications, refer to control drawing 600820 for the US06 series and 610125 for the US01 and US03 series. All control drawing can be found at flowline.com. The cabling should be a shielded twisted pair to minimize EMI interference. Typically 20 to 24 gauge wire is used in this application.
NOTES ON SAFETY Where personal safety or significant property damage can occur due to a spill, the installation must have a redundant backup safety system installed. Wiring should always be completed by a licensed electrician. The transmitter must be chemically compatible with the application. ...
PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR REPRESENTATIONS ON BEHALF OF FLOWLINE. This warranty will be interpreted pursuant to the laws of the State of California. If any portion of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other provision of this warranty.