Configuration ( With Display) - FlowLine EchoPod UG06 Series Manual

Hide thumbs Also See for EchoPod UG06 Series:
Table of Contents

Advertisement

Configuration Using Display
®
EchoPod
can be configured before installation. The transmitter features non-volatile memory, so any setting
configured before installation will not be lost when the switch is powered down. To configure, follow the steps
below:
1. Measure the Tank
a. Begin by measuring the key tank and fitting dimensions.
b. Correct tank dimensions will result in accurate sensor measurement.
2. Set the Units of Measurement (UNITS)
a. Units can be configured in basic engineering units of length including Feet, Inches, Centimeters
or Meters.
3. Set the Sensor Height (HEIGHT)
a. This is the empty setting (4mA) for the tank.
4. Set the Fill-Height (FILL-H)
a. This is the full setting (20mA) for the tank.
5. Set the Fail-Safety (SAFE)
a. This is the maximum measurement range for the sensor. The sensor will ignore all echo returns
beyond this setting.
NOTE:
When configuring EchoPod
accomplish the goal of sensor configuration. Changes to the configuration can be made using the alternative method.
When beginning with one method, it is recommended to complete the configuration before using the other method to
make any adjustments.
|
22
®
, choose either the WebCal
®
or Push Button method.
Step Four
Either method will
MN310140 Rev A3