Network Detection

"Network Detection" detects IO devices on the network and configures PROFINET settings online.
Select the [Network Detection] tab.  [Network]  [Read Network Configuration]
(1)
(2)
(3)
No.
Description
(1)
Indicates the RJ71PN92. Since the RJ71PN92 is not an IO device, it cannot be added in the network configuration settings.
(2)
When this IO device supports the non-connected type Acyclic communication (Implicit Read), slots and sub slots that configure the IO device are also
displayed.
(3)
Since this IO device has an IP address in the class different from the RJ71PN92, it cannot be added in the network configuration settings.
When detecting IO devices on the network, note the following points.
• A name has been set to the IO device, and the name does not duplicate with other IO devices.
• An IP address has been set to the IO device, and the IP address does not duplicate with other IO devices.
• The GSDML file of each IO device has been added in "Device Library". (The PROFINET setting is based on the GSDML
files. When the GSDML files have been added, the PROFINET setting cannot be configured.)
*1 Set names and IP addresses of the IO devices in the "Devices on the Network" window. ( Page 75 "Devices on the Network"
window)
*2 Add GSDML files in the "GSDML Management" window. ( Page 69 Adding IO devices)
Perform the action related to "Network Detection" when it is set online. For the operating procedure, refer to
the following.
Page 98 When adding IO devices online
* 1
* 1
*2
3 GX Configurator-PN
3.1 Window Structure
3
73