Chapter 2 Parameter Settings; Setting Parameters - Mitsubishi Electric MELSEC iQ-R Series User Manual

Profinet io controller module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

2
PARAMETER SETTINGS
This chapter describes the parameter settings required for communications between the RJ71PN92 and IO devices.
2.1

Setting Parameters

1.
Add the RJ71PN92 in the engineering tool.
[Navigation window]  [Parameter]  [Module Information]  Right-click  [Add New Module]
2.
The basic settings and refresh settings are included in the module parameter. Select the settings from the tree in the
following window and configure them. Set the refresh timing in the refresh settings.
[Navigation window]  [Parameter]  [Module Information]  [RJ71PN92]  [Module Parameter]
3.
Start GX Configurator-PN to set PROFINET communication parameters.
[Navigation window]  [Parameter]  [Module Information]  [RJ71PN92]  [PROFINET Module Setting]
4.
Set the refresh settings related to the I/O data exchange of the RJ71PN92. In the refresh settings, assign buffer memory
areas and devices of the CPU module.
[Navigation window]  [Parameter]  [Module Information]  [RJ71PN92]  Right-click  [Autorefresh Settings]
5.
Update global labels and structure related to the RJ71PN92 and register them in the engineering tool.
[Navigation window]  [Parameter]  [Module Information]  [RJ71PN92]  Right-click  [Update PROFINET Label]
6.
Covert or rebuild programs.
[Convert]  [Convert] or [Rebuild All]
7.
Write the settings configured in step 2 to 5 to the CPU module and the RJ71PN92 by using the engineering tool.
[Online]  [Write to PLC]
8.
The settings are reflected by powering off and on or resetting the CPU module.
2 PARAMETER SETTINGS
2.1 Setting Parameters
2
51

Advertisement

Table of Contents
loading

Table of Contents