Mitsubishi Electric MELSEC iQ-R Series User Manual page 149

Profinet io controller module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CPU to PN handshake flag (data consistency setting output area)
■CPU to PN handshake flag (data consistency setting output area) (Un\G17049 to Un\G17056)
This flag is used when the data consistency function is executed. For details on data consistency function, refer to the
following.
Page 20 Data Consistency Function
Address
b15
b14
b13
Un\G17049
15
14
13
Un\G17056
127
126
125
Each number in the table represents an IO device ID. Each bit corresponds to the IO device ID. For IO device IDs, refer to the
following.
Page 82 [General Configuration] tab
Service execution request 1, Service execution request 2
■Service execution request 1, Service execution request 2 (Un\G17057)
These execution request bits are for 'Service request area 1' (Un\G50000 to Un\G52087) and 'Service request area 2'
(Un\G52250 to Un\G54337).
To execute the service, set these areas. For details on the service interface functions, refer to the following.
Page 24 Service Interface Function
Address
Bit
Un\G17057
b0
b1
b2 to b15
Module status
■Module status (Un\G17118 to Un\G17119)
The RJ71PN92 status and errors can be checked.
Address
Bit
Un\G17118
b0
b1 to b2
b3
b4 to b15
Un\G17119
b0
b1 to b15
*1 When parameters are newly written, 1 is set when the CPU module is powered on or reset.
b12
b11
b10
b9
b8
12
11
10
9
8
124
123
122
121
120
Name
Service request area 1 execution
request bit
Service request area 2 execution
request bit
System area
Name
Parameter setting status
System area
Communication start completion
System area
Module error
System area
b7
b6
b5
b4
7
6
5
4
119
118
117
116
Description
0: Do not send execution request to Service request area 1
1: Send execution request to Service request area 1
0: Do not send execution request to Service request area 2
1: Send execution request to Service request area 2
Description
The status of parameter setting of the RJ71PN92 is stored.
0: Parameter setting not completed
1: Parameter setting completed successfully
The communication start status of the RJ71PN92 is stored.
0: Communication start not completed
1: Communication start completed
The error status of the RJ71PN92 is stored.
0: No error
1: Error
b3
b2
b1
b0
3
2
1
0
115
114
113
112
*1
APPX
Appendix 2 Buffer Memory
A
147