The following table lists the response format for when the request of this service has been completed with an error.
Buffer memory address (decimal)
Service response area 1
57000 to 57001
57002
57003
57004 to 57005
57006
57007
57008
57009
*1 Error details can be checked from combinations of ErrorDecode, ErrorCode1, and ErrorCode2. For details, refer to the manuals of the
IO device.
Service response area 2
59250 to 59251
59252
59253
59254 to 59255
59256
59257
59258
59259
Item name
Stored value
RequestID
Value set in the request format
ServiceID
0003H
Status
The cause of the error is stored.
The values are as follows.
• 0001H: Module not started
• 0002H: Not connected to network
• 0003H: IO device not detected
• 0004H: Incorrect data size
• 0006H: IO device not connected
• 0007H: IO device not set
• 0008H: PROFINET error Check ErrorDecode,
ErrorCode1, and ErrorCode2.
• 000BH: Incorrect parameter
DeviceID
0
Data length(byte)
0
ErrorDecode
Value other than 0000H
ErrorCode1
Value other than 0000H
ErrorCode2
Value other than 0000H
*1
*1
*1