3.7.1.2
PROFINET Scanner Parameters (Redundancy Tab)
On the Redundancy tab, select whether or not the PNS is redundantly controlled.
When the PNS supports PROFINET System Redundancy and is configured in an HSB CPU Redundancy system,
the Programmer automatically selects redundant control by setting the Redundancy Mode parameter to HSB
CPU Redundancy.
When the PNS does not support PROFINET System Redundancy, or is not configured in an HSB CPU
Redundancy system, the PNS Programmer automatically selects simplex operation (non-redundant control) by
setting the Redundancy Mode parameter to None.
To configure a redundancy-capable PNS for simplex operation within an HSB CPU Redundancy system, change
the Redundancy Mode parameter on the Redundancy tab from HSB CPU Redundancy to None.
3.7.1.3
PROFINET Scanner Parameters (Media Redundancy Tab)
By default, the PNS is not set up for Media Redundancy. If the system will use Media Redundancy
(see Chapter 6, Redundant Media, for more information), open the Media Redundancy tab and select
Client.
If the PNS will be a Media Redundancy Client, click on Ring Port 1 and Ring Port 2 to choose the module ports
that will be used.
GFK-2571N

Figure 56: PNS Parameters Redundancy Tab

Figure 57: PNS Parameters Media Redundancy Tab
Figure 58: Select PNS Ring Ports Usage
May 2018
Chapter 3. Configuration
67