GE PACSystems RX3i User Manual page 131

Profinet io-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Chapter 5. Diagnostics
Group/
Category/
Description
Type/
Descriptor
7-34-0-0
Addition of
network interface.
7-36-0-0
Addition of
network port.
7-36-1-0
Network port
released by
PROFINET IO
Supervisor.
9-6-10-0
Multiple Media
Redundancy
Managers have
been detected on
the network.
9-6-11-0
Multiple Media
Redundancy
Managers are no
longer present on
the network.
9-6-12-0
The Media
Redundancy
Manager has
detected that the
network ring has
been broken.
9-6-13-0
The Media
Redundancy
Manager has
detected that the
network ring has
been repaired.
9-11-3-1
Invalid MAC
address detected.
9-11-3-3
Media redundancy
configuration error.
120
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
Cause
A configured PROFINET
interface that was
previously reported lost has
been added to the device.
A configured PROFINET
port that was previously
reported lost has been
added to the device.
A configured PROFINET
port that was previously
controlled by a PROFINET
IO Supervisor has been
released.
The PROFINET Controller is
configured as a Media
Redundancy Manager and
other Media Redundancy
Managers are currently
present on the network.
The PROFINET Controller is
configured as a Media
Redundancy Manager and it
had detected that multiple
Media Redundancy
Managers were on the
network, but now those
other managers are no
longer present.
The PROFINET MRP
network ring is broken.
The PROFINET MRP
network ring is closed/okay.
PROFINET Controller no
longer has a valid MAC
address.
The PROFINET Controller
has encountered a problem
attempting to configure
media redundancy
operation.
Recommended
Correction
None.
None.
None.
Update the PROFINET Controller
configuration to change its MRP role
to either Disabled or Client, or remove
all of the other devices on the
network that are also acting as a
Media Redundancy Manager.
No action necessary. The network is
expected to only have a single Media
Redundancy Manager present.
The MRP Ethernet ring is broken.
Possible causes include damaged or
disconnected cable or power loss to a
node or switch. Locate and repair the
cause(s).
No action necessary. This is the
normal, expected state of an MRP
Ethernet ring.
Contact customer service.
Contact customer service.
GFK-2571N

Advertisement

Table of Contents
loading

Table of Contents