Group-
Error
Description
Code
11-83
Module
configuration
mismatch
detected after
module hot-
insertion.
11-84
Configured SFP
mismatch
detected.
13-h
10
PNC001
hardware failure.
135-s
11
PNC001 has
encountered a
critical fatal error.
140-i
12
PNC001 has
encountered a
non-critical error.
h – Error code that provides more information about what part of the PNC's hardware experienced a failure.
10
11
s – Error code that provides more information about what caused a fatal error on the PNC.
12
i – Error code that provides more information about a non-critical error.
GFK-2571N
Cause
A module has been hot-
inserted into a PROFINET
IO-Device, and the
physical module detected
does not match the
configured module.
SFP configured for a port
on the PNC001 does not
match what is physically
present on the PNC001.
The PNC001 has
encountered a hardware
related failure.
A critical fatal error has
occurred during normal
PNC001 operation from
which the PNC001 cannot
recover.
A non-critical error has
occurred on the PNC001.
May 2018
Chapter 5. Diagnostics
Recommended Correction
Either update the configuration stored to the
PROFINET Controller to match the module
physically present, or replace the module on
the IO-Device to match the PME
configuration.
The SFP present should operate properly in
the presence of this fault. However, to
eliminate the fault, either update the
configuration to match the actual SFP type in
use, or physically replace the SFP in use with
the type of SFP configured.
Contact customer service.
Contact customer service.
None. This fault is informational.