Chapter 5. Diagnostics
Group/
Error
Description
Code
8-1
Return of
Submodule
PROFINET Alarm
received.
8-2
PROFINET
Submodule replied
negatively to Plug
configuration.
8-3
PROFINET Controller
failed delivery of
fault to the
PACSystems
controller.
8-5
Failure occurred
while processing
configuration.
8-6
PNIO stack
asynchronous
response error
9-3
Rejected mail error.
9-4
Mail processing
error on the
PROFINET
Controller.
9-7
PROFINET Alarm
processing error
10-1
Module service
request processing
error
112
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
Cause
The PROFINET Controller has received a
Return of Submodule PROFINET alarm from
a PROFINET device.
The PROFINET Controller received a
negative acknowledgement while
attempting to reconfigure a PROFINET
submodule that had been plugged back in to
a device.
The PROFINET Controller was unable to
deliver to the PACSystems controller a fault
that was logged locally on the PROFINET
Controller. The fault will appear in the Local
Log of the PROFINET Controller, but will not
appear in the controller Fault Tables.
The PROFINET Controller experienced a
failure while processing a new configuration.
Note: The PACSystems controller that
delivered the configuration to the
PROFINET Controller should also log
its own unique failure fault in the
Controller Fault Table.
The PROFINET Controller has experienced a
generic error resulting from interactions
with the PROFINET Controller stack.
Possible causes include two or more
messages from the controller stack were
not received in the expected order.
The PROFINET Controller received a rejected
mail message from the CPU.
The PROFINET Controller encountered an
error while processing mail received from
the PACSystems CPU (e.g. PROFINET
Controller received rejected mail from CPU).
The PROFINET Controller has attempted to
ACK/NACK a PROFINET Alarm more than
once.
The PROFINET Controller encountered an
error trying to process a Service Request
from the CPU (e.g. a request to list all
PROFINET devices on the network)
Recommended
Correction
None.
Attempt reactivation of
submodule, by removing
the submodule and
reinserting it into its host
device.
Contact customer service.
Contact customer service.
This is an informational
fault. No action is
required.
Contact customer service.
None.
This is an informational
fault. No action is
required.