Electrical Installation

4.2.1 EMC Interference

4
4
1
Customer control termination points–options A and
B
2
Screened control wiring
3
Cable clamp
4
Customer control input
5
Potential equialisation wire [minimum 16 mm
Figure 4.1 EMC-correct Installation
NOTICE!
EMC Interference
Use screened cables for motor and control wiring. Separate the LHD mains input cable, motor cable, and control wiring.
Minimum 200 mm (7.9 in) clearance between power, motor, and control cables is required. Maximise this clearance to
minimise EMC emissions. This reduces the risk of interference between the LHD and other electronic devices.
36
®
VLT
AutomationDrive FC 302 Low Harmonic Drive
132–630 kW
2
3
10
9
7
6
7
8
9
10
2
]
Danfoss A/S © Rev. 04/2015 All rights reserved.
1
2
3
5
6
3
7
8
6
9
Motor output cable, 3-phase and PE (not screened)
Cable gland
Clearance, minimum 200 mm
Mains input cable, 3-phase and reinforce PE (not screened)
Low harmonic drive (LHD)
4
5
3
2
8
MG37A322