Class 3 relates to compatibility levels greater than the public supply network. This class applies only to IPCs in
industrial environments. Use this class where the following equipment is found:
Typically, a class cannot be defined ahead of time without taking into account the intended equipment and processes to be
used in the environment. VLT
supply system conditions (R
Harmonic order (h)
Table 1.7 Compatibility Levels for Harmonics
THD(V)
Table 1.8 Compatibility Levels for the Total Harmonic Voltage Distortion THD(V)

1.6.5 IEEE Harmonic Standards

The IEEE 519 standard (Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems)
provides specific limits for harmonic voltages and currents for individual components within the supply network. The
standard also provides limits for the sum of all loads at the point of common coupling (PCC).
To determine permissible harmonic voltage levels, IEEE 519 uses a ratio between the supply short-circuit current and the
maximum current of the individual load. For permissible harmonic voltage levels for individual loads, see Table 1.9. For
permissible levels for all loads connected to the PCC, see Table 1.10.
I
/I
(R
)
SC
L
SCE
10
20
50
100
1000
Table 1.9 Permissible Voltage THD at the PCC for Each Individual Load
Voltage at the PCC
V
≤69 kV
Line
Table 1.10 Permissible Voltage THD at the PCC for all Loads
Limit harmonic currents to specified levels, as shown in Table 1.11. IEEE 519 utilises a ratio between the supply short-circuit
current and the maximum current consumption at the PCC, averaged over 15 minutes or 30 minutes. In certain instances
18
-
Large converters.
-
Welding machines.
-
Large motors starting frequently.
-
Loads that change quickly.
®
AutomationDrive FC 302 Low Harmonic Drive observes the limits of Class 3 under typical
>10 or
SC
Vk Line
5
7
11
13
17
17˂h≤49
2.27 x (17/h) – 0.27
Permissible individual harmonic voltages
Danfoss A/S © Rev. 04/2015 All rights reserved.
®
VLT
AutomationDrive FC 302 Low Harmonic Drive
132–630 kW
<10%).
Class 1 (V
%)
h
3
3
3
3
2
Class 1
5%
2.5–3%
2.0–2.5%
1.0–1.5%
0.5–1%
0.05–0.1%
Permissible individual harmonic voltages
3%
Class 2 (V
%)
h
6
5
3.5
3
2
2.27 x (17/h) – 0.27
Class 2
8%
Typical areas
Weak grid
1–2 large loads
A few high-output loads
5–20 medium-output loads
Strong grid
Permissible THD(V)
5%
Class 3 (V
%)
h
8
7
5
4.5
4
4.5 x (17/h) – 0.5
Class 3
10%