Motor Bearing Currents; Ac Mains Connection; Ac Line Input Connections; External Fan Supply - Danfoss VLT AutomationDrive FC 302 Installation Manual

Low harmonic drive 132–630 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Electrical Installation

4.6.4 Motor Bearing Currents

Motors with a rating 110 kW or higher combined with
adjustable frequency drives are best with NDE (Non-Drive
End) insulated bearings to eliminate circulating bearing
currents caused by motor size. To minimize DE (Drive End)
bearing and shaft currents, proper grounding is required
4
4
for:
Adjustable frequency drive
Motor
Motor-driven machine
Motor to the driven machine
Although failure due to bearing currents is infrequent, use
the following strategies to reduce the likelihood:
Use an insulated bearing
Apply rigorous installation procedures
Ensure that the motor and load motor are aligned
Strictly follow the EMC Installation guideline
Reinforce the PE so the high frequency
impedance is lower in the PE than the input
power leads.
Provide a good high frequency connection
between the motor and the adjustable frequency
drive
Ensure that the impedance from adjustable
frequency drive to building ground is lower than
the grounding impedance of the machine. Make
a direct ground connection between the motor
and load motor.
Apply conductive lubrication
Try to ensure that the line voltage is balanced to
ground.
Use an insulated bearing as recommended by the
motor manufacturer (note: motors from reputable
manufacturers typically have insulated bearings
as standard in motors of this size).
If found to be necessary and after consultation with
Danfoss:
Lower the IGBT switching frequency
Modify the inverter waveform, 60° AVM vs. SFAVM
Install a shaft grounding system or use an
isolating coupling between motor and load
Use minimum speed settings, if possible.
Use a dU/dt or sinus filter
40
®
VLT
AutomationDrive FC 302 Low Harmonic Drive
132–630 kW

4.7 AC Mains Connection

4.7.1 AC line input connections

Line power must be connected to terminals 91, 92 and 93
on the far left of the unit. Ground is connected to the
terminal on the right of terminal 93.
Terminal No.
91, 92, 93
94
Table 4.5 Terminal Functions
Ensure that the power supply can supply the necessary
current to the adjustable frequency drive.
If the unit is without built-in fuses, ensure that the
appropriate fuses have the correct current rating.

4.7.2 External Fan Supply

If the adjustable frequency drive is supplied by DC or the
fan must run independently of the power supply, use an
external power supply. Make the connection on the power
card.
Terminal No.
100, 101
102, 103
Table 4.6 Terminal Functions
The connector on the power card provides the connection
of line voltage for the cooling fans. The fans are connected
from the factory to be supplied from a common AC line
(jumpers between 100–102 and 101–103). If external
power supply is needed, remove the jumpers and connect
the supply to terminals 100 and 101. Protect with a 5 A. In
UL applications, use a Littelfuse KLK-5 or equivalent.
Danfoss A/S © Rev. 04/2015 All rights reserved.
Function
Line power R/L1, S/L2, T/L3
Ground
Function
Auxiliary supply S, T
Internal supply S, T
MG37A322

Advertisement

Table of Contents
loading

Table of Contents